IRC R319.2.1 (2021: R310.2.1)
Minimum net clear opening area
≥ 5.7 sq ft net clear opening; 5 sq ft for a grade-floor opening
“Emergency escape and rescue openings shall have a net clear opening of not less than 5.7 square feet (0.530 m2). Exception: The minimum net clear opening for grade-floor emergency escape and rescue openings shall be 5 square feet (0.465 m2).”
The 2018 IRC exception read "Grade floor openings or below-grade openings shall have a net clear opening area of not less than 5 square feet", so under 2018 every below-grade opening qualified for 5 sq ft.
IRC Chapter 2 definition
What counts as a grade-floor opening
Grade floor = bottom of the opening within 44 in above or below outside ground
“GRADE FLOOR EMERGENCY ESCAPE AND RESCUE OPENING. An emergency escape and rescue opening located such that the bottom of the clear opening is not more than 44 inches (1118 mm) above or below the finished ground level adjacent to the opening.”
IRC R319.2.2 (2021: R310.2.2)
Minimum clear height and width
Clear height ≥ 24 in and clear width ≥ 20 in, by normal operation
“The minimum net clear opening height dimension shall be 24 inches (610 mm). The minimum net clear opening width dimension shall be 20 inches (508 mm). The net clear opening dimensions shall be the result of normal operation of the opening.”
IRC R319.2.3 (2021: R310.2.3)
Maximum height from the floor
Bottom of the clear opening ≤ 44 in above the floor
“Emergency escape and rescue openings shall have the bottom of the clear opening not greater than 44 inches (1118 mm) above the floor.”
The 2018 IRC (R310.2.2) said a window "shall have a sill height of not more than 44 inches (1118 mm) above the floor". Since 2021 the measurement is to the bottom of the clear opening, not the sill trim.
IRC R319.1.1 (2021: R310.1.1)
Opens without keys, tools or special knowledge
Opens from inside without keys, tools or special knowledge
“Emergency escape and rescue openings shall be operational from the inside of the room without the use of keys, tools or special knowledge.”
Window opening control devices and fall prevention devices complying with ASTM F2090 are permitted, mounted not more than 70 inches above the finished floor.
IRC R319.4 (2021: R310.4)
When a window well is required
A well is required when the bottom of the opening is below the ground outside
“An emergency escape and rescue opening where the bottom of the clear opening is below the adjacent grade shall be provided with an area well in accordance with Sections R319.4.1 through R319.4.4.”
IRC R319.4.1 (2021: R310.4.1)
Minimum window well size
Well ≥ 9 sq ft, with width and projection each ≥ 36 in; the window must open fully
“The horizontal area of the area well shall be not less than 9 square feet (0.9 m2), with a horizontal projection and width of not less than 36 inches (914 mm). The size of the area well shall allow the emergency escape and rescue opening to be fully opened.”
Exception: the required ladder or steps may encroach not more than 6 inches into the required dimensions of the well.
IRC R319.4.2 (2021: R310.4.2)
Ladder or steps in deep wells
Wells deeper than 44 in need a permanently affixed ladder or steps
“Area wells with a vertical depth greater than 44 inches (1118 mm) shall be equipped with an approved, permanently affixed ladder or steps. The ladder or steps shall not be obstructed by the emergency escape and rescue opening where the window or door is in the open position.”
IRC R319.4.2.1 (2021: R310.4.2.1)
Ladder rungs
Rungs ≥ 12 in wide inside, ≥ 3 in off the wall, ≤ 18 in apart
“Ladders and rungs shall have an inside width of not less than 12 inches (305 mm), shall project not less than 3 inches (76 mm) from the wall and shall be spaced not more than 18 inches (457 mm) on center vertically for the full height of the area well.”
IRC R319.4.3 (2021: R310.4.3)
Window well drainage
Well drains to the foundation drainage system (unless on Group I soils)
“Area wells shall be designed for proper drainage by connecting to the building’s foundation drainage system required by Section R405.1.”
Exception: no drainage system is required where the foundation is on well-drained soil or sand-gravel mixture soils (Group I soils).
IRC R319.4.4 (2021: R310.4.4)
Bars, grilles, covers and screens
Covers, bars and grilles release from inside without a key, tool or extra force
“Such devices shall be releasable or removable from the inside without the use of a key or tool or force greater than that required for the normal operation of the escape and rescue opening.”
IRC R319.2.4 (2021: R310.2.4)
Openings under decks, porches and cantilevers
Under a deck or porch: fully openable, with a 36 × 36 in path out
“Emergency escape and rescue openings installed under decks, porches and cantilevers shall be fully openable and provide a path not less than 36 inches (914 mm) in height and 36 inches (914 mm) in width to a yard or court.”
The 2018 IRC required a path 36 inches in height only, and did not mention cantilevers.
IRC R319.1 (2021: R310.1)
Where an egress opening is required
Required in basements and every sleeping room (with listed exceptions)
“Basements, habitable attics, the room to which a sleeping loft is open, and every sleeping room shall have not less than one operable emergency escape and rescue opening. Where basements contain one or more sleeping rooms, an emergency escape and rescue opening shall be required in each sleeping room.”
Exceptions include basements used only to house mechanical equipment and not over 200 sq ft, storm shelters built to ICC 500, and basement sleeping rooms in a home with an automatic sprinkler system where the basement has the required second way out. The 2024 edition added "the room to which a sleeping loft is open".
IRC R319.7 (2021: R310.7)
Remodeling an existing basement
Finishing an existing basement triggers one only for a new bedroom
“New sleeping rooms created in an existing basement shall be provided with emergency escape and rescue openings in accordance with Section R319.1. Other than new sleeping rooms, where existing basements undergo alterations or repairs, an emergency escape and rescue opening is not required.”
IRC R319.5 (2021: R310.5)
Replacement windows
A replacement window can be exempt from the size rules
“The replacement window is the manufacturer’s largest standard size window that will fit within the existing frame or existing rough opening.”
A replacement window meeting this condition (and not part of a change of occupancy) is exempt from the size rules of R319.2 and the cover rule of R319.4.4. It may keep the same operating style, or use a style with an equal or greater opening.